ETS-Lindgren's Medical RF Filters enable electrical power, lighting and data signals to be brought into the MRI room, through the RF shield. All RF filters are typically located in one area, usually near the penetration panel of the MRI equipment. Below are the most common medical RF filters used, however ETS-Lindgren can provide virtually any filter you may need. UL, ULC and CE filters are also available, including low current leakage filters.
Facility filters allow specified frequencies to pass while suppressing or attenuating other frequencies. The filters listed as ELUL, EQ and LMF are our most common models utilized in medical applications. There are many other versions of RF filters also available for a wide variety of applications. Our complete line of RF filters incorporates a wide array of choices which provide effective EMI/RFI shielding to meet or exceed industry standards.
|
|
|
---|
Model |
ELUL-2030 (Power, Light) |
EQ-2001-NR (Smoke, Fire, Thermo.) |
EQ-2010-1C (ERDU, EPO) | LMF-4112 | |||
---|---|---|---|---|---|---|---|
Part Number |
E-ELUL-2030 |
E-EQ-2001-NR |
E-EQ-2010-1C |
E-WLMF-4112 | |||
Number of Lines |
2 |
2 |
2 | 2 | |||
Weight | 6.8 kg (15.0 lb) |
|
|
| |||
Dimension A | 53.98 cm (21.25 in) |
38.74 cm (15.25 in) | 38.74 cm (15.25 in) | 38.74 cm (15.25 in) | |||
Dimension B | 52.71 cm (20.75 in) |
37.47 cm (14.75 in) |
37.47 cm (14.75 in) |
37.47 cm (14.75 in) | |||
Dimension C | 50.8 cm (20.0 in) | 35.56 cm (14.0 in) | 35.56 cm (14.0 in) | 35.56 cm (14.0 in) | |||
Dimension D | 12.7 cm (5.0 in) | 7.62 cm (3.0 in). | 7.62 cm (3.0 in) | 7.62 cm (3.0 in) | |||
Dimension E | 7.62 cm (3.0 in) | 5.08 cm (2.0 in) |
5.08 cm (2.0 in) | 5.08 cm (2.0 in) | |||
Dimension F | 3.96 cm (1.56 in) | 3.81 cm (1.5 in) | 3.81 cm (1.5 in) |
3.81 cm (1.5 in) | |||
Dimension G |
7.62 cm (3.0 in) |
5.08 cm (2.0 in) |
5.08 cm (2.0 in) |
5.08 cm (2.0 in) |
Model |
ELUL-2030 (Power, Light) |
EQ-2001-NR (Smoke, Fire, Thermo.) |
EQ-2010-1C (ERDU, EPO) | LMF-4112 |
---|---|---|---|---|
Part Number | E-ELUL-2030 | E-EQ-2001-NR | E-EQ-2010-1C | E-WLMF-4112 |
Rated Current (Amps) | 0 to 30 | 0 to 1.0 | 0 to 10 | 0 to 30 |
Max. Leakage Current @220 V, 50 Hz | 700 mA | 3 mA | 3 mA | N/A |
Max. Leakage Current @120 V, 60 Hz | 450 mA | 1.5 mA | 1.5 mA | N/A |
Rated Voltage | 0-277/480 VAC/VDC | 0-30/50 VAC/VDC | 0-250/250 VAC/VDC | 0-250/250 VAC/VDC |
Insertion Loss | 100 dB min. from 150 kHz to 40 GHz per MIL-STD-220. | 100 dB min. from 150 kHz to 40 GHz per MIL-STD-220. | 100 dB min. from 150 kHz to 40 GHz per MIL-STD-220. | 100 dB min from 30 MHz - 40 GHz per MIL-STD-220 |
Voltage Drop | Not to exceed 1% of applied voltage at Unity Power Factor. | Not to exceed 1% of applied voltage at Unity Power Factor. | Not to exceed 1% of applied voltage at Unity Power Factor. | Not to exceed 1% of applied voltage at Unity Power Factor. |
Safety | Discharge resistors provided per UL-1283. | Discharge resistors provided per UL-1283. | Discharge resistors provided per UL-1283. | Discharge resistors provided per UL-1283. |
Passband Impedance | N/A | N/A | N/A | N/A |